ASSEMBLY, INSTALLATION & SERVICING MANUAL
FOR AMBIRAD VISION
®
VSO & VSXO
R
ANGE OF RADIANT TUBE HEATERS
INDEX Section
Introduction and Document Index
Installation Requirements-------------------------------------------------1
Assembly Instructions------------------------------------------------------2
Commissioning Instructions----------------------------------------------3
Servicing Instructions------------------------------------------------------4
Spare Parts-------------------------------------------------------------------5
Fault Finding Guide --------------------------------------------------------6
Replacing Parts -------------------------------------------------------------7
User and Operating Instructions ----------------------------------------8
WARNINGS
AmbiRad equipment must be installed and maintained in accordance with the relevant
provisions of the Gas Safety (Installations and Use) Regulations 1998 for gas fired products.
Due account should also be taken of any obligations arising from the Health and Safety at
Works Act 1974 or relevant codes of practice. In addition the installation must be carried out
in accordance with the current IEE wiring regulations (BS 7671), BS 6896 (Industrial &
Commercial) and any other relevant British Standards and Codes of Practice by a qualified
installer. All external wiring MUST comply with the current IEE wiring regulations.
Zobrazit stránku 0
1 2 3 4 5 6 ... 59 60

Shrnutí obsahu

Strany 1 - OF RADIANT TUBE HEATERS

1 ASSEMBLY, INSTALLATION & SERVICING MANUAL FOR AMBIRAD VISION® VSO & VSXO RANGE OF RADIANT TUBE HEATERS INDEX Section Introduction and D

Strany 2

10 1.6 Clearance to Combustibles. The minimum clearances to combustible materials are given in the tables below. These minimum distances MUST

Strany 3 - Document Index

11 Figure 5.b Clearance to combustibles Vision Optima Unitary VSO UT FDABCDIM 'C'DIM 'C'DIM 'B'DIM 'C'VSO UT

Strany 4

12 Figure 5.c Clearance to combustibles Vision Optima Herringbone VSO UH FDABCDIM 'C'DIM 'C'DIM 'B'DIM 'C'VSO

Strany 5

13 to the heater not to apply excessive turning force to the internal controls. A flexible hose is installed to allow safe linear expansion of the he

Strany 6 - 305.0457.0

14 Depending on the specific installation, the flexible gas hose may be routed to the gas cock at any of the following angles in relation to the bur

Strany 7

15 Figure 7.b Typical VSOUT Induced Unitary Wiring Connections (end covers not shown) Figure 7.e Typical VSXO Powered burner Wiring Connections (end c

Strany 8 - Hole Centers Hole Centers

16 MAIN J.S.T.YELLOWGREYWHITEFLAME SENSORIGNITER8791110 121324BLACKPINKWHITELAMPSONBURNERGREYYELLOWBLACKGRN/YELBROWNSOLENOID VALVESWITCHN.C.N.O.C.GREY

Strany 9

17 Figure 9. Typical VSO UH Schematic Wiring Connections 1.9 Ventilation Requirements AmbiRad tube heaters can be operat

Strany 10 - 20/25 30/35/40

18 1.10 Flue and Combustion Air Inlet - Options Dependent on the type of burner fitted to your heater it is possible to have configurations of flue

Strany 11 - 15/20/25 30/35/40

19 The maximum distance between supports is 1.5m for horizontal runs. Wall bands are not load bearing and give lateral support only. If used, wall ba

Strany 13 - +/- 20mm

20 Option 1 - Figure 10a. Air Inlet Attachments Unitary Herringbone Burners (VSO) For non-flued installations, delete items A and B and rotate fan out

Strany 14 - 1.8 Electrical Connection

21 Option 2 - Figure 10b. Air Inlet Attachments Induced Herringbone Burners (VSO) A Induced Burner B Air Intake (supplied as standard) C Optional Du

Strany 15

22 Ventilation requirements are as detailed in section 1.9 Option 3 - Figure 10c. Forced Burner with Heat Exchanger (VSXO Standard Flue) For flued pr

Strany 16

23 Ventilation requirements are as detailed in section 1.9 Ducted air must be used in locations where there is airborne dust or where there is a po

Strany 17 - 1.9 Ventilation Requirements

24 Option 5 - Figure 10e. Forced Burner with Heat Exchanger (with Concentric Flue) E Forced Burner F Heat Exchanger G 100mm (4ins) Clips x2 H 100mm

Strany 18

25 1.11 Technical Details. Table 5. Burner Settings - Natural Gas (G20) Heater Model Heat Input kW Gas Flowrate (m³/hr) Injector Pressure (mbar) Inje

Strany 19 - 1.10.3 Condensation

26 Heater Model Cold HB Pressure Hot HB Pressure mm H2O mbar mm H2O mbar VSO20UH 18.4 1.8 10.2 1.0 VSO25UH 25.5 2.5 17.3 1.7 VSO30UH 14.3 1.4 10

Strany 20

27 Heater Model Heat Input kW Flowrate (l/hr) Injector Pressure (mbar) Injector Size (mm) *Size (h x l x w) * Weight (Kg) Gross Nett VSO15UH 15.0 13

Strany 21

28 Heater Model Mass Flow Rate of Flue Gasses (kg/s) Flue Pressure (Pa) Maximum Flue Resistance Flue Gas Temp (°C) VSO15UT 0.0152 12.5 182 VSO20UT 0

Strany 22

29 2. Assembly Instructions. PLEASE READ this section prior to assembly to familiarise yourself with the components and tools you require at th

Strany 23

3 Introduction. Welcome to the new range of high efficiency AmbiRad Vision radiant tube heaters. Local regulations may vary in the country of use and

Strany 24

30 2.2.4 Couplers For fixing the U bend. Locate and position tube couplers (D) Slide the coupler over the components ensuring that the rivet s

Strany 25 - 1.11 Technical Details

31 1200 CRS. 1785 CRS. 2321785 CRS.1235 CRS.1795 CRS.1235 CRS. 1235 CRS. 1120 CRS. 1235 CRS. 1785 CRS.232232BURNERENDBURNERENDBURNERENDBABBBBBBBBBBB B

Strany 26

32 2.2.6 U Bend. Slide U bend (C) into the open end of the couplers ensuring the pre-fitted bolts engage in the precut holes. Tighten all four cl

Strany 27

33 BAREFLECTOR #2BABBAAREFLECTOR #1REFLECTOR #1REFLECTOR #3REFLECTOR #2REFLECTOR #1REFLECTOR #4REFLECTOR #2REFLECTOR #32019312019281200 OVERSHIELD1680

Strany 28

34 2.2.7.2 Inner Reflectors 2.2.7.2.1 Two Module units 1. Place inner reflectors (H) on the heater by sliding the reflectors between the tubes a

Strany 29 - 2. Assembly Instructions

35 2.2.8 Insulation mats. Using the recommended safety equipment i.e. gloves, goggles and a face mask, cover the back of reflectors with the insulati

Strany 30 - Locknut

36 TWOMODULETHREEMODULEFOURMODULE114mm OVERLAP67mm OVERLAP77mm OVERLAP84mm OVERLAP77mm OVERLAP50mm OVERLAPWASHERREFLECTORWASHERREFLECTOR FIXINGDETAIL-

Strany 31

37 other and insert M8 self tapping screws provided. 6. Repeat the procedure for 3rd set of outer canopies. 2.2.9.3 Four Module Unit

Strany 32 - 2.2.7 Reflectors

38 *CANOPY FIXINGFOUR MODULE ONLYPOSITION EFOURMODULETHREEMODULESCRAP PLAN VIEWFROM ABOVE HEATER30mm OVERLAP30mm OVERLAP30mm OVERLAP90mm OVERLAP30mm O

Strany 33 - FIXED - POSITION B

39 2.2.10 End Caps Position the end cap with no tube holes (M) beneath the reflector profile at the U bend end making sure that the end cap e

Strany 34 - Four Module Units

4 1.1 Health and Safety AmbiRad heaters must be installed in accordance with the relevant provisions of the Gas Safety (Installation

Strany 35 - 2.2.8 Insulation mats

40 2.2.15 Fixing of optional End Mouldings. If end mouldings (P) have been ordered (optional item) fit the end mouldings with the screws provided /

Strany 36 - Fig. 13 Reflector detail

41 Fig. 15 Two Module drawings A B C G P J1 J2 D H J3 K L M N F1 E1 E2 E3 F2 H Reflectors J1 Overshields J2 Expansion Plate J3 Cross Member K Insulati

Strany 37 - 2.2.9 Outer Canopy's

42 Ref Description A Radiant Tubes B Suspension Brackets C Return Bend D Couplers E1 Heat Exchanger (VXSO) E2 Fan (unitary heaters) E3 Damper (Herrin

Strany 38 - Fig. 14 Canopy detail

43 Ref Description A Radiant Tubes B Suspension Brackets C Return Bend D Couplers E1 Heat Exchanger (VXSO) E2 Fan (unitary heaters) E3 Damper (Herrin

Strany 39

44 3.2 Balancing The Herringbone System Important. When all the heaters have been installed the vacuum settings must be finally balanced in the hot

Strany 40

45 Slacken screw in burner lid and open the right hand burner access door. The two vacuum impulse hoses are in view. Both hoses are fitted with ‘T’ p

Strany 41 - Fig. 15 Two Module drawings

46 Check installation has been carried out to these instructions. NO YES Ensure gas and electricity supplies are isolated. Disconnect gas hose from bu

Strany 42 - (optional)

47 Small Flat Head Screwdriver 4. Servicing Instructions. These appliances should be serviced annually by a competent person to ensure safe and effic

Strany 43 - Fig. 17 Four Module drawings

48 4.3 Burner Removal (All Options) Step 1 Isolate mains electric and gas supplies. Step 2 Detach the gas supply as shown below, taking care to

Strany 44 - Description

49 Step 3 On forced burners with ducted air attachment, slacken jubilee clip and remove flexible hose from the fan. Step 4 Slacken both grub scr

Strany 45

5 Figure 1.b. Recommended Methods of Heater Suspension. Where chain supports have an angle of inclination greater than 15° an equal and opposite suppo

Strany 46 - 3.3 Commissioning chart

50 Step 2 The pepper pot burner head can be replaced ensuring the 5 holes on the outer ring are aligned alongside the probes. Step 3 The condition of

Strany 47 - 4. Servicing Instructions

51 Step 4 Inspect the impeller and remove any dust with a soft brush. Step 5 Remove any dust from fan scroll and from around the motor. Step 6 Ensure

Strany 48

52 Step 4 Withdraw the turbulators from the appliance. Carefully noting their condition and position. Replace turbulators if necessary. Step 5

Strany 49

53 Required Spares (refer to section 4.2) In order to aid troubleshooting and servicing we recommend that the components shown in this section should

Strany 50

54 6. Fault Finding Guide. Check: 1. Integrity of spark leads 2. Integrity of electrode assembly & spark gap 3. Burner controller Ensure gas &

Strany 51

55 7. Replacing Parts. 7.1.1 Burner Controller Replacement (VSXO) Step 1 Slacken screw in burner lid and open the right hand burner access door. Ste

Strany 52

56 7.2 Air Pressure Switch Replacement Step 1 Disconnect the two silicone impulse tubes and three wiring connections making note of replacement posit

Strany 53 - 5. Spare Parts

57 Step 7 Remove the four screws holding the rear burner plate in position plus the two screws from the gas valve flange. Step 8 Remove the rear plat

Strany 56

6 1.5 Herringbone Systems (VSOUH). The manifold system should be arranged to fall slightly in the direction of the vacuum fan. This ensures that any

Strany 57

60 8.1 To Start the Heater 1. Ensure gas supply is turned on. 2. Electrical supply to the controls is on. 3. Ensure that the controls are correctl

Strany 58

7 For details of fan mounting bracket and fixing down holes see figure 3. Figure 2e. Conventional Flue Arrangement Roof Exit. Figure 2f. Conventional

Strany 59

8 Fig 2c/d Figure 3. Vacuum Fan Mounting Details (Type ‘O’ fan illustrated) Hole Centers Hole Centers Fan Type O Type 2 A 124 80 B 38 35 C 175

Strany 60

9 Figure 4. Typical Herringbone system (VSO shown with optional end covers) Dos Don’ts Check for corrosive industrial process in proposed